Your generator’s weak point isn’t watts. It’s gallons.
Everybody shops for a generator by how much it can run. In a long outage the question that matters is how long your fuel lasts.
In short: A generator burns fuel whether the house is using its power or not. Honda’s own figures show a small generator makes about 58% more electricity per gallon at full load than at a quarter load. Run it hard into a battery, then shut it off.
By Bret, founder of Bugging Out Solar, on the Outer Banks of North Carolina
After a big storm the gas stations are closed or have lines around the block. Whatever fuel you stored is what you have. So the generator that looks best on the shelf, the one that can run everything at once, can be the one that runs you dry first.
A big generator, sitting there
A 22-kilowatt home standby generator burns about 2.5 gallons of propane an hour at half load and about 3.9 at full load, by the maker’s spec sheet. At half load around the clock that is about 61 gallons a day. A 500-gallon tank is only filled to about 80%, so it holds roughly 400 gallons. That is under a week.
And most of the day the house is not asking for half of 22 kilowatts. It is asking for a refrigerator, some lights and a fan, while the engine keeps turning.
A small generator, used two ways
Take a Honda EU2200i, a common small generator. Honda lists a 0.95-gallon tank that lasts 8.1 hours at a quarter load and 3.2 hours at its full rated load of 1,800 watts.
Work that out and the difference is large. At a quarter load it makes about 3.8 kilowatt-hours from a gallon. At rated load it makes about 6.1. That is about 58% more electricity from the same gallon.
Say the house needs about 10.8 kilowatt-hours a day, which is what that generator makes running at a quarter load for 24 hours. Running all day that way burns about 2.8 gallons. Making the same energy at full load takes 6 hours and about 1.8 gallons.
That only works with somewhere to put the power
A house can’t use six hours of full output on a schedule. A battery can. The generator runs hard for a few hours and fills the battery, then shuts off. The battery carries the house in silence until it needs filling again. You burn about a gallon less a day in this example, the engine runs a quarter of the hours, and the neighbors get some sleep.
Some of that gain is lost in charging the battery, so the real saving is a little smaller than the arithmetic. It is still the single biggest way to stretch stored fuel. The battery can be a home battery, a power station (often sold as a “solar generator”), or the one in an electric truck. Try your own setup in the backup power calculator, which shows generator hours per day with and without a battery.
If all you have is a small portable generator, the simplest way to do this is covered in pair it with a solar generator.
One thing to do today
Find your generator’s manual and look up its run time at a quarter load and at full load. Divide the tank size by each to see what it burns per hour. Then count how many gallons you have stored.
The numbers
| What | Figure |
|---|---|
| Honda EU2200i tank | 0.95 gallons |
| Run time at a quarter load | 8.1 hours |
| Run time at rated load (1,800 watts) | 3.2 hours |
| Electricity per gallon at a quarter load | About 3.8 kilowatt-hours (our arithmetic) |
| Electricity per gallon at rated load | About 6.1 kilowatt-hours (our arithmetic) |
| 22 kW standby generator on propane, half load | About 2.5 gallons an hour |
| 22 kW standby generator on propane, full load | About 3.9 gallons an hour |
| Usable propane in a 500-gallon tank | About 400 gallons |
For reporters
Use the numbers and quote this piece freely. All we ask is a link back to this page. To reach us, use the form at Talk to Us.
Sources